UPS 20KVA (3 IN/3 Out) Online Low frequency | UPS 20KVA (3 IN/3 Out)

$3,999.00

  • High intelligent product integrating digitization & network
  • Powerful information acquisition system, signal system, detection system & perfect protection system
  • Online dual conversion with inbuilt isolation transformer
  • Computer or network remote control trobleshoot wit inbuilt dry-contact signal, remote control signal.
  • N+X redundant control tech eliminates the single point failure in system
Categories: , ,

Description

Online Low frequency UPS 20KVA (3 IN/3 Out)

Features:

  • High intelligent product integrating digitization & network
  • Powerful information acquisition system, signal system,ย detection system & perfect protection system
  • Online dual conversion with inbuilt isolation transformer
  • Computer or network remote control trobleshoot wit inbuiltย dry-contact signal, remote control signal.
  • N X redundant control tech eliminates the single pointย failure in system

Application:

  • Critical servers
  • Network station
  • Process control
  • Laboratory instruments
  • Data center front maintenance design
  • Medical instruments
  • Industrial equipment

Technical Parameter:

Model GE
SS10S
GE
SS15S
GE
SS20S
GE
SS30S
GE
SS40S
GE
SS60S
GE
SS80S
GE
SS100S
GE
SS120S
GE
SS160S
GE
SS200S
Capacitry 10KVA
/8KW
15KVA
/12KW
20KVA
/16KW
30KVA
/24KW
40KVA
/32KW
60KVA
/48KW
80KVA
/64KW
100KVA
/80KW
120KVA
/96KW
160KVA
/128KW
200KVA
/160KW
Phase 3-phase in / 3-phase out
Input Rated Voltage 3 x 380VAC/400VAC
Input Voltage Range 285VAC-475VAC
Input Frequency 50/60Hz ยฑ 10%
Output voltage 3 x 380VAC/400VAC
Output Phase Single-Phase(1Ph N G)
Output Wave Pure Sine Wave
Output Steady Voltage ยฑ 1%
Output Dynamic Voltage ยฑ 5%
Output frequency 50Hz/60HZ ยฑ 1%
Output frequency accuracy ยฑ 1%
Output frequency tracking range ยฑ 5Hz
Output frequency tracking speed 1-2 Hz/s
Output power factor 0.8
Output crest factor 3:01
Output voltage distortion linear load <2% , non-linear load <5%
Output transient recovery time <60ms recover to 90%
Output transfer time 0ms
Output overload protection 110%-150%, 10min to 1min; 150%-160%, 1min to 200ms; >160%,200ms
Output short circuit protection 60-100ms
Output transient response < 5ms
Protection overioad, over charge and over discharge, out of the range of valtage and fraquency, over current, short circuit, over temperature, ect.
System specification efficiency(AC mode) 89% 90% 91% 92%
System specification efficiency(Battery mode) 90% 91% 92% 93%
Bypass type Static switch
Bypass Voltage 3 x 380VAC/400VAC
Bypass frequency 50/60 Hz
Bypass control method microprocessor
Inversion to bypass transfer time 0ms(synchronous mode); 10ms (Asynchronous mode)
Bypassoverioad protection 1.5-1.8, between 1h to 30s
Bypass short circuit protection 1.8- >2.0, between 30s to 200ms
transfer to bypass overload 160%
transfer to inversion alarm clear
Battery quantity 29/30/31/32
Battery charging mode Constant voltage charging / Constant current charging
Battery charging current 10A 40A
Battery type Lead-acid battery / Nickel-chromium battery
Operating temperature (-)15-60ยบC
Operating humidlty 0-90%
Noise < 70dB @ 1 Meter
Dimension 655*405*817 655*405*941 821*432*1159 975*554*1286 1051*705*1646
Weight 118 120 133 193 256 297 400 472 573 717 735

Reviews

There are no reviews yet.

Be the first to review “UPS 20KVA (3 IN/3 Out) Online Low frequency | UPS 20KVA (3 IN/3 Out)”

Your email address will not be published. Required fields are marked *